LOGO! 0BA7 型号中的新功能:
SIPLUS extreme 产品基于 SIMATIC 标准产品。此处的内容摘自相关的标准产品。增加了与 SIPLUS extreme 相关的信息
|
Order number |
6AG1052-1CC01-2BA6 |
6AG1052-1MD00-2BA6 |
6AG1052-1HB00-2BA6 |
6AG1052-1FB00-2BA6 |
|
|---|---|---|---|---|---|
|
SIPLUS LOGO! 24C |
SIPLUS LOGO! 12/24RC |
SIPLUS LOGO! 24RC |
SIPLUS LOGO! 230RC |
||
|
Display |
|
|
|
|
|
|
with display |
Yes; The display is bright at temperatures below 0 °C and dark at temperatures over +55 °C. This procedure is self-reversing on returning to the standard temperature range (0 °C to +55 °C). |
Yes; The display is bright at temperatures below 0 °C and dark at temperatures over +55 °C. This procedure is self-reversing on returning to the standard temperature range (0 °C to +55 °C). |
Yes; The display is bright at temperatures below 0 °C and dark at temperatures over +55 °C. This procedure is self-reversing on returning to the standard temperature range (0 °C to +55 °C). |
Yes; The display is bright at temperatures below 0 °C and dark at temperatures over +55 °C. This procedure is self-reversing on returning to the standard temperature range (0 °C to +55 °C). |
|
|
Installation type/mounting |
|
|
|
|
|
|
Mounting |
on 35 mm DIN rail, 4 spacing units wide |
on 35 mm DIN rail, 4 spacing units wide |
on 35 mm DIN rail, 4 spacing units wide |
on 35 mm DIN rail, 4 spacing units wide |
|
|
Supply voltage |
|
|
|
|
|
|
Rated value (DC) |
|||||
|
Yes |
||||
|
Yes |
Yes |
Yes |
||
|
Yes |
||||
|
Yes |
||||
|
permissible range, lower limit (DC) |
20.4 V; 22 V @ >55 °C |
10.8 V; 11 V @ >55 °C |
20.4 V; 22 V @ >55 °C |
100 V |
|
|
permissible range, upper limit (DC) |
28.8 V; 27.5 V @ >55 °C |
28.8 V; 27.5 V @ >55 °C |
28.8 V; 27.5 V @ >55 °C |
253 V |
|
|
Rated value (AC) |
|||||
|
Yes |
||||
|
Yes |
||||
|
Yes |
||||
|
Time of day |
|
|
|
|
|
|
Time switching clocks |
|
|
|
|
|
|
190 |
8 |
|||
|
80 h |
80 h |
80 h |
80 h |
|
|
Digital inputs |
|
|
|
|
|
|
Number of digital inputs |
8; Of which 4 can be used in analog mode (0 to 10 V) |
8; Of which 4 can be used in analog mode (0 to 10 V) |
8 |
8 |
|
|
Digital outputs |
|
|
|
|
|
|
Number of digital outputs |
4; Transistor |
4; Relays |
4; Relays |
4; Relays |
|
|
Short-circuit protection |
Yes; electrical (1 A) |
No; external fusing necessary |
No; external fusing necessary |
No; external fusing necessary |
|
|
Output current |
|
|
|
|
|
|
0.3 A; 0.2 A @ > 55 °C; 0.3 A @ > 55 °C & < 15 s |
||||
|
Relay outputs |
|
|
|
|
|
|
Switching capacity of contacts |
|
|
|
|
|
|
3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s |
3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s |
3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s |
||
|
10 A; 3 A per relay @ > 55 °C; 10 A per relay @ > 55 °C & < 15 s |
10 A; 3 A per relay @ > 55 °C; 10 A per relay @ > 55 °C & < 15 s |
10 A; 3 A per relay @ > 55 °C; 10 A per relay @ > 55 °C & < 15 s |
||
|
EMC |
|
|
|
|
|
|
Emission of radio interference acc. to EN 55 011 |
|
|
|
|
|
|
Yes; Radio interference suppression according to EN55011, Limit Value Class B |
Yes |
Yes |
Yes |
|
|
Degree and class of protection |
|
|
|
|
|
|
Degree of protection acc. to EN 60529 |
|||||
|
Yes |
Yes |
Yes |
Yes |
|
|
Standards, approvals, certificates |
|
|
|
|
|
|
CSA approval |
No |
No |
No |
No |
|
|
UL approval |
Yes; File: E120869 // Tmax = 55 °C |
Yes; File: E120869 // Tmax = 55 °C |
Yes; File: E120869 // Tmax = 55 °C |
Yes; File: E120869 // Tmax = 55 °C |
|
|
FM approval |
No |
No |
No |
No |
|
|
developed in accordance with IEC 61131 |
Yes |
Yes |
Yes |
Yes |
|
|
according to VDE 0631 |
Yes |
Yes |
Yes |
Yes |
|
|
Marine approval |
|
|
|
|
|
|
No |
No |
No |
No |
|
|
Ambient conditions |
|
|
|
|
|
|
Ambient temperature during operation |
|
|
|
|
|
|
-25 °C; = Tmin |
-25 °C; = Tmin |
-25 °C; = Tmin |
-25 °C; = Tmin |
|
|
70 °C; = Tmax; 55 °C @ UL/cUL use |
70 °C; = Tmax; 55 °C @ UL/cUL use |
70 °C; = Tmax; 55 °C @ UL/cUL use |
70 °C; = Tmax; 55 °C @ UL/cUL use |
|
|
Extended ambient conditions |
|
|
|
|
|
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
|
|
Relative humidity |
|
|
|
|
|
|
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
|
|
Resistance |
|
|
|
|
|
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
|
|
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation! |
|
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
|
|
Dimensions |
|
|
|
|
|
|
Width |
72 mm |
72 mm |
72 mm |
72 mm |
|
|
Height |
90 mm |
90 mm |
90 mm |
90 mm |
|
|
Depth |
55 mm |
55 mm |
55 mm |
55 mm |
|
|
Order number |
6AG1052-1MD00-2BA7 |
6AG1052-1FB00-2BA7 |
|
|---|---|---|---|
|
SIPLUS LOGO!12/24RCE |
SIPLUS LOGO! 230RCE |
||
|
Display |
|
|
|
|
with display |
Yes |
Yes |
|
|
Installation type/mounting |
|
|
|
|
Mounting |
on 35mm DIN rail, 6 spacing units wide |
on 35mm DIN rail, 6 spacing units wide |
|
|
Supply voltage |
|
|
|
|
Rated value (DC) |
|||
|
Yes |
||
|
Yes |
||
|
Yes |
||
|
Yes |
||
|
permissible range, lower limit (DC) |
10.8 V |
100 V |
|
|
permissible range, upper limit (DC) |
28.8 V |
253 V |
|
|
Rated value (AC) |
|||
|
Yes |
||
|
Yes |
||
|
Time of day |
|
|
|
|
Time switching clocks |
|
|
|
|
333 |
333 |
|
|
480 h |
480 h |
|
|
Digital inputs |
|
|
|
|
Number of digital inputs |
8; of which 4 can be used in analog mode (0 to 10 V); max. load 9 A per relay @ all DI @ +55 °C to +60 °C; max. load 1 A per relay @ all DI @ > +60 °C; max. load 3 A per relay @ half the number of DI @ > +60 °C |
8; half the number of DI @ max. load 1A per relay @ > +60 °C |
|
|
Digital outputs |
|
|
|
|
Number of digital outputs |
4; Relays |
4; Relays |
|
|
Short-circuit protection |
No; external fusing necessary |
No; external fusing necessary |
|
|
Relay outputs |
|
|
|
|
Switching capacity of contacts |
|
|
|
|
3 A |
3 A |
|
|
10 A; max. last 9 A per relay @ all DI @ +55 °C to +60 °C; max. load 1 A per relay @ all DI @ > +60 °C; max. load 3 A per relay @ half the number of DI @ > +60 °C |
10 A; max. load 1A per relay @ half the number of DI @ > +60 °C |
|
|
EMC |
|
|
|
|
Emission of radio interference acc. to EN 55 011 |
|
|
|
|
Yes; Radio interference suppression according to EN55011, Limit Value Class B |
Yes; Radio interference suppression according to EN55011, Limit Value Class B |
|
|
Degree and class of protection |
|
|
|
|
Degree of protection acc. to EN 60529 |
|||
|
Yes |
Yes |
|
|
Standards, approvals, certificates |
|
|
|
|
CSA approval |
Yes |
||
|
UL approval |
Yes |
Yes |
|
|
FM approval |
Yes |
||
|
developed in accordance with IEC 61131 |
Yes |
Yes |
|
|
according to VDE 0631 |
Yes |
Yes |
|
|
Marine approval |
|
|
|
|
Yes |
||
|
Ambient conditions |
|
|
|
|
Ambient temperature during operation |
|
|
|
|
-25 °C; = Tmin |
-25 °C; = Tmin |
|
|
70 °C; = Tmax |
70 °C; = Tmax |
|
|
Extended ambient conditions |
|
|
|
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
|
|
Relative humidity |
|
|
|
|
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
|
|
Resistance |
|
|
|
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
|
|
Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
|
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
|
|
Dimensions |
|
|
|
|
Width |
107 mm |
107 mm |
|
|
Height |
90 mm |
90 mm |
|
|
Depth |
55 mm |
55 mm |
|